ABB AC500 PLC Hardware Manual page 1251

Table of Contents

Advertisement

2.6.1.4
Power Supply Units
For the supply of the modules, power supply units according to PELV specifications must be
used.
2.6.1.5
Electromagnetic Compatibility
Electromagnetic Compatibility
Device suitable for:
Immunity against electrostatic discharge (ESD):
Immunity against the influence of radiated (CW
radiated):
Immunity against fast transient interference vol-
tages (burst):
Immunity against the influence of line-conducted
interferences (CW conducted):
2019/04/17
Industrial applications
Domestic applications
Electrostatic voltage in case of air discharge
Electrostatic voltage in case of contact dis-
charge
ESD with communication connectors
ESD with connectors of Terminal Bases
Test field strength
Supply voltage units (DC)
Supply voltage units (AC)
Digital inputs/outputs (24 VDC)
Digital inputs/outputs (120 VAC...240 VAC)
Analog inputs/outputs
CS31 system bus
Serial RS-485 interfaces (COM)
Serial RS-232 interfaces (COM, not for PM55x
and PM56x)
ARCNET
FBP
Ethernet
I/O supply (DC-out)
3ADR010121, 13, en_US
System Assembly, Construction and Connection
AC500 (Standard) > System Data AC500
Yes
No
According to IEC 61000-4-2, zone B,
criterion B
8 kV
4 kV, in a closed switch-gear cabinet 6
kV
1
)
In order to prevent operating malfunc-
tions, it is recommended, that the oper-
ating personnel discharge themselves
prior to touching communication con-
nectors or perform other suitable
measures to reduce effects of electro-
static discharges.
The connectors between the Terminal
Bases and Processor Modules or
Communication Modules must not be
touched during operation. The same is
valid for the I/O-Bus with all modules
involved.
According to IEC 61000-4-3, zone B,
criterion A
10 V/m
According to IEC 61000-4-4, zone B,
criterion B
2 kV
2 kV
1 kV
2 kV
1 kV
1 kV
1 kV
1 kV
1 kV
1 kV
1 kV
1 kV
According to IEC 61000-4-6, zone B,
criterion A
1251