2.6.1.4
Power Supply Units
For the supply of the modules, power supply units according to PELV specifications must be
used.
2.6.1.5
Electromagnetic Compatibility
Electromagnetic Compatibility
Device suitable for:
Immunity against electrostatic discharge (ESD):
Immunity against the influence of radiated (CW
radiated):
Immunity against fast transient interference vol-
tages (burst):
Immunity against the influence of line-conducted
interferences (CW conducted):
2019/04/17
Industrial applications
Domestic applications
Electrostatic voltage in case of air discharge
Electrostatic voltage in case of contact dis-
charge
ESD with communication connectors
ESD with connectors of Terminal Bases
Test field strength
Supply voltage units (DC)
Supply voltage units (AC)
Digital inputs/outputs (24 VDC)
Digital inputs/outputs (120 VAC...240 VAC)
Analog inputs/outputs
CS31 system bus
Serial RS-485 interfaces (COM)
Serial RS-232 interfaces (COM, not for PM55x
and PM56x)
ARCNET
FBP
Ethernet
I/O supply (DC-out)
3ADR010121, 13, en_US
System Assembly, Construction and Connection
AC500 (Standard) > System Data AC500
Yes
No
According to IEC 61000-4-2, zone B,
criterion B
8 kV
4 kV, in a closed switch-gear cabinet 6
kV
1
)
In order to prevent operating malfunc-
tions, it is recommended, that the oper-
ating personnel discharge themselves
prior to touching communication con-
nectors or perform other suitable
measures to reduce effects of electro-
static discharges.
The connectors between the Terminal
Bases and Processor Modules or
Communication Modules must not be
touched during operation. The same is
valid for the I/O-Bus with all modules
involved.
According to IEC 61000-4-3, zone B,
criterion A
10 V/m
According to IEC 61000-4-4, zone B,
criterion B
2 kV
2 kV
1 kV
2 kV
1 kV
1 kV
1 kV
1 kV
1 kV
1 kV
1 kV
1 kV
According to IEC 61000-4-6, zone B,
criterion A
1251