Device Specifications
Communication Interface Modules (S500) > CANopen
Parameter
Indication of the input/output signals
Galvanic isolation
Technical data
Please refer to the Technical Data of the Digital Inputs. Deviation:
of the digital
Terminals of the channels DC0 to DC7: Terminals 2.0 to 2.7
inputs/outputs if
used as inputs
Due to the direct connection to the output, the demagnetizing varistor is also effective at the
input. This is why the difference between UPx and the input signal must not exceed the clamp
voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V. Consequently, the
input voltage must range from -12 V to +30 V when UPx = 24 V and from -6 V to +30 V when
UPx = 30 V.
Technical data
Please refer to the Technical Data of the Digital Outputs. Deviation:
of the digital
Terminals of the channels DC0 to DC7: Terminals 2.0 to 2.7
inputs/outputs if
used as outputs
The following drawing shows the circuitry of a digital input/output with the varistors for demag-
netization when inductive loads are switched off.
Fig. 137: Digital input/output (circuit diagram)
1
2
Technical Data of the Fast Counter
Parameter
Used inputs
Used outputs
Counting frequency
Detailed description
Operating modes
758
Digital input/output
For demagnetization when inductive loads are turned off
3ADR010121, 13, en_US
Value
1 yellow LED per channel, the LED is ON
when the input/output signal is high (signal 1)
From the CANopen network
UPx (+24 V)
1
ZPx (0 V)
2
Value
Terminal 3.0 (DI8), 3.1 (DI9)
Terminal 4.0 (DO8)
Depending on operation mode:
Mode 1 - 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
Ä Chapter 1.5.1.2.10 "Fast
Fast Counter
Counter" on page 394
Ä Chapter 1.5.1.2.10 "Fast
Operating modes
Counter" on page 394