ABB AC500 PLC Hardware Manual page 669

Table of Contents

Advertisement

LED
1.6.2.1.9
Technical Data
The System Data of AC500 and S500
valid for standard version.
The System Data of AC500-XC
valid for the XC version.
Only additional details are therefore documented below.
Parameter
Process supply voltage
Current consumption
Galvanic isolation
Max. power dissipation within the
module
Weight (without terminal unit)
Mounting position
Cooling
2019/04/17
State
CH-ERR1,
CH-ERR2,
CH-ERR4
CH-ERR *) Error indica-
tion
*) All LEDs CH-ERR1, CH-ERR2 and CH-ERR4 light up simultaneously
Connections
Protection against reverse
voltage
Rated protection fuse at UP
Rated value
Max. ripple
From UP
Via I/O bus
Inrush current from UP (at
power-up)
3ADR010121, 13, en_US
Color
LED = OFF
Red
Serious
error within
the corre-
sponding
group
Red
Internal
error or con-
figuration is
not loaded
Ä Chapter 2.6.1 "System Data AC500" on page 1248 are
Ä Chapter 2.7.1 "System Data AC500-XC" on page 1309 are
Value
Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24 VDC) and 1.9,
2.9, 3.9 and 4.9 for ZP (0 V)
Yes
10 A fast
24 VDC
5 %
0.07 A + max. 0.008 A per input + max. 0.5 A per output +
0.01 A for A, B and Z inputs
Ca. 5 mA
0.04 A²s
Yes, per module
6 W (outputs unloaded)
Ca. 125 g
Horizontal mounting or vertical with derating (output load
reduced to 50 % at 40 °C)
The natural convection cooling must not be hindered by
cable ducts or other parts in the switch-gear cabinet.
Device Specifications
Function Modules > S500
LED = ON
LED flashes
No error or
Error on one
process
channel of the
voltage is
corresponding
missing
group (e.g.
short circuit at
an output)
--
---
669