It is useful, to activate both the pull-up and the pull-down resistors, which only are necessary
once on every bus line, at the bus master.
Pin assignment
Serial
Interface
The following drawing shows an RS-485 bus with the bus master at the line end.
1
Master at the bus line end, pull-up and pull-down activated, bus termination with 120 Ω
resistors
2
Slave within the bus line
3
Slave at the bus line end, bus termination with 120 Ω resistors
If the master is located within the bus line, it does not need a terminating resistor. The pull-up
and the pull-down resistors, however, are necessary:
2019/04/17
Pin
Signal
1
FE
2
TxD
3
RxD/TxD-P
4
RTS
5
SGND
6
+5 V
7
RxD
8
RxD/TxD-N
9
CTS
Shield
FE
NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist
environments.
Protect unused connectors and slots with TA535 protective caps for XC devices
Ä Chapter 1.8.4.6 "TA535 - Protective Caps for XC Devices"
TA535
on page 1172.
3ADR010121, 13, en_US
System Assembly, Construction and Connection
AC500 (Standard) > Connection and Wiring
Interface
Description
-
Functional earth
RS-232
Transmit data
RS-485
Receive/Transmit
RS-232
Request to send
Signal ground
0 V supply out
-
5 V supply out
RS-232
Receive data
RS-485
Receive/Transmit
RS-232
Clear to send
-
Functional earth
Output
Positive
Output
Input
Negative
Input
1281