ABB AC500 PLC Hardware Manual page 1037

Table of Contents

Advertisement

1.7.6.2.9
Measuring Ranges
Input Ranges Voltage, Current and Digital Input
Range
Overflow
Measured
value too high
Normal range
Normal range
or measured
value too low
Measured
value too low
Underflow
Range
Overflow
Measured value too high
Normal range
Normal range or measured
value too low
Measured value too low
Underflow
The represented resolution corresponds to 16 bits.
2019/04/17
0...10 V
-10...+10 V
>11.7589
>11.7589
11.7589
11.7589
:
:
10.0004
10.0004
10.0000
10.0000
:
:
0.0004
0.0004
0.0000
0.0000
-0.0004
-0.0004
-1.7593
:
:
:
-10.0000
-10.0004
:
-11.7589
<0.0000
<-11.7589
Digital value
Decimal
32767
32511
:
27649
27648
:
1
0
-1
-4864
-6912
:
-27648
-27649
:
-32512
-32768
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFINET
0...20 mA
4...20 mA
>23.5178
>22.8142
23.5178
22.8142
:
:
20.0007
20.0006
20.0000
20.0000
:
:
0.0007
4.0006
0
4
3.9994
:
0
<0.0000
<0.0000
Hex.
7FFF
7EFF
:
6C01
6C00
:
0001
0000
FFFF
ED00
E500
:
9400
93FF
:
8100
8000
Device Specifications
Digital input
On
Off
1037