Fig. 61: Connection example
With the 3-wire configuration, two adjacent analog channels belong together (e.g. the channels
0 and 1). In this case, both channels are configured according to the desired operating mode.
The lower address must be the even address (channel 0), the next higher address must be the
odd address (channel 1).
The constant current of one channel flows through the resistance thermometer. The constant
current of the other channel flows through one of the cores. The module calculates the meas-
ured value from the two voltage drops and stores it under the input with the higher channel
number (e.g. I1).
In order to keep measuring errors as small as possible, it is necessary to have all the involved
conductors in the same cable. All the conductors must have the same cross section.
Pt100
Pt100
Pt1000
Ni1000
The I/O module performs a linearization of the resistance characteristic.
In order to avoid error messages from unused analog input channels, it is useful to configure
them as "unused".
2019/04/17
Pt100
Pt1000
Ni1000
UP
ZP
If several measuring points are adjacent to each other, only one return line is
necessary. This saves wiring costs.
-50 °C...+70 °C
-50 °C...+400 °C
-50 °C...+400 °C
-50 °C...+150 °C
3ADR010121, 13, en_US
I/O Modules > Analog I/O Modules
1.0
2.0
I0-
I0+
1.1
2.1
I1-
I1+
PTC
1.8
2.8
UP
UP
1.9
2.9
ZP
ZP
3-wire configuration, two
channels used
3-wire configuration, two
channels used
3-wire configuration, two
channels used
3-wire configuration, two
channels used
Device Specifications