Starting up the device - Configuration
8.12.5 Module 70 – Switching input SWI1
PROFINET-IO module identifier
Module ID: 1070
Submodule ID: 1
NOTICE
Module 70 functions only as a switching input.
Parameter
Tab. 8.40:
Parameters for module 70
Parameter
Inversion
Reserved
Debounce time
Start-up delay
Minimum switch-
on time
Switch-off delay
Input function
Parameter length
23 bytes
Input data
None
Output data
None
Comment
The bias level also defines whether the output is low-active (0) or high-active (1).
Switching on an output means switching to the active state; switching off, on the other hand, results in
switching to the inactive or idle state.
Leuze electronic GmbH + Co. KG
Description
The parameter defines the logic
of the incident signal. In case of
an inversion, an external HIGH
level is interpreted internally as a
LOW level.
Free
The parameter defines a de-
bounce time in ms which is im-
plemented in software.
The parameter influences the
time behavior in ms during
switch-on.
The parameter defines a mini-
mum time period in ms before
the signal is reset.
The parameter defines a time
delay in ms for the signal during
switch-off.
The parameter specifies the
function which is to be activated
or deactivated by a status
change in the signal.
Addr. Data type
13.1
Bit
13.2
... 13.
7
14
UN-
SIGNED16
16
UN-
SIGNED16
18
UN-
SIGNED16
20
UN-
SIGNED16
22
UNSIGNED8 see chapter
BCL 248i
Value range
Default
0: Normal
0
1: Inverted
0 ... 1000 ms
5 ms
0 ... 65535 ms
0 ms
0 ... 65535 ms
0 ms
0 ... 65535 ms
0 ms
1
8.12.4 "Input
functions for op-
eration as an in-
put"
90