NOTICE
No integrated parameter memory!
No parameter memory is integrated in connection hood KB 307.
Remove the system plug (JST) at the end of the cable.
Connect the connection cable to your SSI interface.
7.5
Pin assignment
7.5.1
PWR / SW IN/OUT (Power and switching input/output)
5-pin, M12 plug (A-coded) or terminal block for connecting to PWR / SW IN/OUT.
Figure 7.4:
PWR / SW IN/OUT connection
Table 7.1:
Pin/terminal
1
2
3
4
5
Thread (M12 plug)
Cable gland
Connection cables: see table 14.3
CAUTION
UL applications!
For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code).
Leuze electronic
5
2
1
FE
3
4
PWR / SW IN/OUT pin assignment
Designation
VIN
SWIO1
GNDIN
SWIO2
FE
Functional earth
4
2
1
3
5
Assignment
+18 ... +30 VDC supply voltage
Sw. input/output 1 (configurable)
Negative supply voltage (0 VDC)
Sw. input/output 2 (configurable)
Functional earth
Connection cable shield.
The shield of the connection cable is on the thread of
the M12 plug or on the screw fitting of the cable bush-
ing.
The thread or the screw fitting is part of the metallic
housing. The housing is at the potential of the func-
tional earth via pin 5.
BPS 307i
Electrical connection
46