Viking Oxeo Installation And Maintenance Manual page 95

Inert gas extinguishing system
Table of Contents

Advertisement

FIGURE 5-14: Assembly on the QRV valve
1. Electrical release device
2. QRV support bracket
3. Pipe clamp QRV
4. Washers
5. M5 x 20 cylinder bolts
6. QRV valve
7. Screws
8. Pressure relief bore
2. Hand-tighten the electrical release device onto the QRV valve.
3. Attach the holder QRV to the QRV valve using a pipe clamp QRV, two M5 x 20 cylinder bolts
and two washers.
WARNING Danger due to incorrectly assembled pipe clamp
Make sure that the pressure relief bore of the QRV valve is visible through the extended
hole of the pipe clamp.
4. Position the limit switch on the electrical release device so that the limit switch actuates prop-
erly but does not exceed its maximum activation path. Securely tighten the limit switch in this
position using the screws.
5. Tighten the electrical release device using a suitable tool and a torque of 25 ± 4 Nm (18.44 ±
2.95 ft-lb).
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
89