Extinguishing Cylinder With Quick Release Valve Qrv; Safety Valve - Viking Oxeo Installation And Maintenance Manual

Inert gas extinguishing system
Table of Contents

Advertisement

9.1 Extinguishing cylinder with quick release valve QRV

Fault description
The value indicated
is too low or too high
Loss indication
shown on the EST/
FACP
Line breakage or
short circuit in the
loss monitoring is
shown on the EST/
FACP

9.2 Safety valve

Fault description
The lead seal or
sealing wire is
damaged
166
Cause
The room temperature is
too low or too high
At least one extinguishing
agent container is leaky
(See above)
Line or cable connection is
faulty
Cause
External influence, e.g.
during the assembly or
servicing
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
Remedy
Adjust the room air-
conditioning
Identify the extinguishing
agent container
Replace the extinguishing
agent container immediately
Identify damaged area and
repair it
Remedy
Replace the safety valve
Personnel
Person in charge
of system
Person in charge
of system
Authorized
Distributor
Authorized
Distributor
Personnel
Authorized
Distributor