Refilling - Viking Oxeo Installation And Maintenance Manual

Inert gas extinguishing system
Table of Contents

Advertisement

Table: Temperature-pressure table IG-100, 4351 psi (300 bar)
Enclosure temperature
[°F]
-4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
131
*Values rounded to whole numbers

8.6 Refilling

Personnel:
Authorized Distributor
Protective equipment:
Industrial hard hat
Safety goggles
Safety gloves
162
IG-100 (N
= nitrogen)
2
Rated filling pressure*
[°C]
[psi]
-20
3539
-15
3655
-10
3771
-5
3887
0
4003
5
4119
10
4235
15
4351
20
4467
25
4583
30
4699
35
4815
40
4731
45
5047
50
5163
55
5279
4351 psi (300 bar)
Pressure* with 10% loss
[bar]
[psi]
244
3176
252
3278
260
3394
268
3495
276
3597
284
3713
292
3815
300
3916
308
4018
316
4119
324
4235
332
4337
340
4438
348
4540
356
4641
364
4743
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
[bar]
219
226
234
241
248
256
263
270
277
284
292
299
306
313
320
327

Advertisement

Table of Contents
loading

Related Products for Viking Oxeo

Table of Contents