Viking Oxeo Installation And Maintenance Manual page 78

Inert gas extinguishing system
Table of Contents

Advertisement

Pipelines, fittings and fastenings are part of the pipeline system. The manufacturer does not
lay out the pipeline system. It must be individually executed by the Authorized Distributor in
accordance with local regulations.
The system components fit the pipeline components that are offered by the manufacturer. If
pipelines other than the offered pipelines are used, these must be selected, installed, and con-
nected in accordance with locally valid regulations.
The pipeline system must be installed in accordance with the design data before the
system components are installed.
Design criteria
Always comply with the following when designing the pipeline system:
The pipeline system must be able to withstand the required system pressures. Take pres-
sure hammers into account.
Select materials and diameters of pipelines in accordance with VdS2380 and ISO14520 and
NFPA2001 and other locally applicable regulations. Here, special attention must be paid to
the compressive strength.
Install pipeline systems in accordance with the hydraulic calculation.
Heed recoil due to discharge nozzles.
Avoid unnecessary angles.
Clean the pipeline system in the course of installation.
Protect the pipeline system against corrosion.
Seal the pipeline system with a suitable, locally approved and recognized sealant.
Provide equipotential bonding.
Do not suspend objects from pipelines.
Structural changes of the protected enclosure require a new design of the entire sys-
tem including the pipeline system.
72
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en