Viking Oxeo Installation And Maintenance Manual page 102

Inert gas extinguishing system
Table of Contents

Advertisement

1. Quick release valve
2. gasket
3. Union nut
9. Check that the gasket is correctly inserted into the hexagonal union nut.
10. Screw the hexagonal union nut onto the quick release valve using a size 30 flat wrench.
FIGURE 5-21: Protective caps and electrical release device
1. Quick release valve
2. Plastic protective cap
3. Connector plug
4. Electrical release device
5. Plastic protective cap
11. Remove plastic protective caps from the quick release valve and from the electrical
release device.
12. Disconnect the connector plug from the electrical release device and connect to electric-
ity.
96
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en