Viking Oxeo Installation And Maintenance Manual page 85

Inert gas extinguishing system
Table of Contents

Advertisement

FIGURE 5-5: Removing plug
1. Contact pressure gauge
2. Quick release valve QRV
3. Pressure gauge connection, connection thread M12 x 1
4. Plug
1. Remove the plug at the pressure gauge connection.
2. Manually screw in the contact pressure gauge into the pressure gauge connection until it can
no longer be turned easily.
FIGURE 5-6: Screwing in the contact pressure gauge
1. Size 14 flat
2. Proper positioning of flat
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
79

Advertisement

Table of Contents
loading

Related Products for Viking Oxeo

Table of Contents