Testing The Function Of Qrv Actuation; Checking The Functioning Of The Pneumatic Time Delay - Viking Oxeo Installation And Maintenance Manual

Inert gas extinguishing system
Table of Contents

Advertisement

7.2 Testing the function of QRV actuation

Personnel:
Authorized Distributor
Material:
Release device QRV reset tool (part no. 934652)
Test device for pneumatic actuation (any air supply under 144 psi)
1. Apply power to the electrical release device QRV to activate the device and pop the release pin
into the active position.
2. Use the reset tool to reset the release pin back into the non-active position.
FIGURE 7-1: Release pin deactivated (A) and activated (B)
1. Marking
2. Release pin

7.3 Checking the functioning of the pneumatic time delay

Personnel:
Authorized Distributor
Protective equipment:
Safety goggles
Safety gloves
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
145

Advertisement

Table of Contents
loading

Related Products for Viking Oxeo

Table of Contents