Viking Oxeo Installation And Maintenance Manual page 83

Inert gas extinguishing system
Table of Contents

Advertisement

1. Remove the extinguishing agent container from the transport frame or from the pallet and
place into the support frame for the extinguishing agent container using a suitable transport
method.
2. Secure the extinguishing agent container from falling over using mounting brackets.
Screw in the mounting brackets until the extinguishing agent container CANNOT fall
but can still be adjusted.
3. Unscrew the valve protection cap from the extinguishing agent container.
4. Align the extinguishing agent containers using the valve output.
5. Repeat the process for all extinguishing agent containers.
6. Tighten all mounting brackets.
5.4.2 Assembling the hose
FIGURE 5-3: Assembling the hose onto the manifold
1. Check valve
2. Seal
3. Hose union
1. Insert a new seal in the union nut G3/4 of the hose union.
2. Screw the hose union onto the check valve until hand-tight.
CAUTION Property damage due to excessive stress on the hose
Do not subject the hose to torsion. Do not go below the minimum bending radius. Do not exceed the
maximum bending angle.
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en