Service Report; Activities Before Servicing - Viking Oxeo Installation And Maintenance Manual

Inert gas extinguishing system
Table of Contents

Advertisement

In addition, maintain components that are subject to wear such as hoses, and so on, in
accordance with the applicable local regulations.
Check extinguishing agent containers
Check extinguishing agent containers in accordance with locally applicable regula-
tions for checking pressure vessels. Have visibly damaged extinguishing agent con-
tainers, and those that show deep corrosion in the floor area checked without delay
and replace them with new containers, if necessary.

8.2 Service report

A service report must be kept concerning the execution of the inspection and maintenance tasks.
The following applies in this regard:
Log execution of all inspection and maintenance tasks in the service report.
Note damaged or non-functioning parts in the service report.
Have the service report countersigned after conclusion of the tasks by the person in charge of
the system.
Give a copy of the service report to the person in charge of the system.
A sample template for such a service report is provided in the Appendix of this man-
ual.

8.3 Activities before servicing

In advance
Servicing must be announced in advance and prepared for:
Inform the operator of the pending servicing in advance.
Inform the operator that the automatic relaying of alarms must be deactivated for the time of
the servicing.
Obtain information on incidents (fires, malfunctions, conversions, spatial changes and changes
in use, etc.).