Viking Oxeo Installation And Maintenance Manual page 167

Inert gas extinguishing system
Table of Contents

Advertisement

4. Check the tightness of the unions.
8.5.2 Checking the fire suppression system center visually
1. Check that the documentation is available at the control panel.
2. Check that the installer sign is present and in a clearly legible condition.
3. Check whether the room temperature is within the designated temperature range (see "Oper-
ating Conditions" on page 181)
4. Check that the markings and warning signs are present and are in a clearly legible condition.
5. Check that the fire extinguishing system control panel is secured against unauthorized access.
6. Check that the lighting is intact and adequate.
7. Check that no objects are stored in the fire extinguishing system control panel and that the fire
extinguishing system control panel is not exposed to any damaging environmental influences.
8. Check that the nameplates of the components are present and in clearly legible condition and
that the emergency service sticker is up-to-date.
9. Check that the function of the system is not impaired by external installations or objects and
that external installations or objects cannot cause a faulty release.
10. Check that the external condition of the extinguishing agent containers, hoses and fixings is
free of faults.
11. Check that the pipeline is grounded and that the ground connection is mechanically intact.
12. Check that the content of the extinguishing agent container is within the tolerances. Read
the pressure gauges taking into account the room temperature and the temperature-pressure
table; for example, see "Table: Temperature-pressure table IG-100, 4351 psi (300 bar)" on page 162
(additional tables are available from the manufacturer).
13. Check the protective coating of the system parts and, if necessary, re-coat.
161
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en