6.8 Limit switch connections to monitored circuits per NFPA

FIGURE 6-9: Limit switches with flexible metal cable conduit
1. Connection socket
2. Fitting for flexible metal cable conduit
3. Flexible metal cable conduit
4. Fitting for flexible metal cable conduit
5. Limit switch
For monitored electrical circuits as per NFPA, the wiring between the limit switch and the connec-
tion socket must be protected by a flexible metal cable conduit. The flexible metal cable conduit
must be fastened with suitable fittings.
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en