FIGURE 5-8: Connecting the master extinguishing agent container to the slave extinguishing
agent container
1. Master extinguishing agent container
2. Sequence valve connection
3. Flexible pilot hose
4. Sealing cone
5. Straight union GE
6. Slave extinguishing agent container
2. Screw the straight union into the sequence valve connection and tighten with a torque of
12 x 1 Nm (8.85 x 0.74 ft-lb).
3. Remove the threaded plugs from the control connections for the quick release valves on
the slave extinguishing agent container.
4. Screw the straight unions into the control connections and tighten with a torque of 12 x 1
Nm (8.85 x 0.74 ft-lb).
5. Assemble an L-union with sealing cone on the straight union on all slave extinguishing
agent containers and align with the connection facing forwards.
6. Connect the master extinguishing agent container and the first slave extinguishing agent
container using the flexible pilot hose.
82
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en