1. Fasten the holder of the blocking device to a wall with the provided screws and plugs.
Do not fasten the blocking device on other system parts.
FIGURE 5-30: Mounting the blocking device (device includes two limit switches, part number
878070D)
1. Cylinder screws
2. Limit switch
3. Blocking device connection
4. Directional indicator
5. Blocking device connection
2. Screw blocking device with the included cylinder screws and hexagon nuts to the holder so
that the marking of the flow direction corresponds to the intended pilot gas flow.
The blocking device has an integrated vent. If the flow direction (arrow) is not heeded,
the blocking device will not work properly.
3. Bolt the pilot line with the cap nut to the two connections of the blocking device.