Pneumatic control device
FIGURE 4-19: Pneumatic control device
1. Steel cylinder (pilot cylinder) UL/FM QRV-TD 80 l N
Contact pressure gauge UL Oxeo 2901 psi (200 bar), NO under pressure (part no. 927612)
Contact pressure gauge UL Oxeo 2901 psi (200 bar), NC under pressure (part no. 927615)
2. Release device, electrical, QRV (part no. 914027D)
3. Pneumatic pilot line (precision steel pipe)
4. Monitoring of electric release device QRV
The pneumatic control device is installed standing on the floor and fastened to a wall using a
wall bracket set. The pneumatic control device is activated by an electrical release device.
When activated, a release pin is activated in the electric release device. The release pin opens
the pilot cylinder valve. The control gas then flows through the pressure reducer into the con-
nected pneumatic pilot line to the pneumatic system parts of the fire extinguishing system.
54
200 EU (part no. 4003404)
2
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en