FIGURE 5-31: Terminal assignment and switching path diagram
1. Contact closed
2. Contact opened
3. Positive opening path/angle

5.11 Mounting the pressure reducer

Personnel:
Authorized Distributor
Protective equipment:
Safety gloves
Safety footwear
WARNING Risk of malfunctioning
The pressure reducer can only fulfill its function in conjunction with the complete system. Every devi-
ation of the system from the design calculation (e.g. different nozzle holes) can restrict the function
of the pressure reducer. This can lead to severe injuries or even death, as well as significant property
damage.
• Never seal the output of the pressure reducer or of the following pipe system.
• In case of deviation of the system from the calculation (e.g. course of pipeline, quantity of extin-
guishing agent, flooding time, extinguishing gas), re-design the pressure reducer.
• Heed the flow direction of the pressure reducer marked by a directional arrow.