Inert gas extinguishing system
Table of Contents

Advertisement

FIGURE 5-28: Installation examples - pilot pressure relief SFD 300
1. Transition screw
2. Transition screw
3. Adapter M12 x 1.5-G1/8 (For pneumatic or pneumatic/manual release device)
NOTICE Property damage due to incorrect assembly
Integrate the safety device upright at all times into the pilot line. Install the safety device as close as
possible to a point of possible leakage (e.g.control gas container).
Assembly in the pilot line
1. Connect the pilot pressure relief to the union.
WARNING Risk of injury due to incorrect installation
Make sure that the safety device is positioned vertically pointing upward.
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en