4.6.5 Contact pressure gauge "extinguishing agent container"
FIGURE 4-11: Contact pressure gauge
1. Green area notating 10% pressure loss
Each valve has a connection for a contact pressure gauge. This connection is closed with a plug.
Pressure gauges must be ordered separately from the cylinders.
Since the connection is fitted with a check valve, the contact pressure gauge can be assembled
even if the extinguishing agent container is pressurized.
The automatic loss monitoring is set to a 10% pressure loss (scale area marked in green) based on
the nominal filling pressure.
Part no.
Nominal pressure
927612
2901 psi (200 bar)
927615
2901 psi (200 bar)
927616
4351 psi (300 bar)
921617
4351 psi (300 bar)
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
Pressure range
Switching point
4351 psi (300 bar)
2611 psi (180 bar)-
NO under pressure
4351 psi (300 bar)
2611 psi (180 bar)-
NC under pressure
6527 psi (450 bar)
3916 psi (270 bar)-
NO under pressure
6527 psi (450 bar)
3916 psi (270 bar)-
NC under pressure