9. Assemble an L-union with sealing cone on the straight union on the last slave extinguish-
ing agent container and align with the connection facing upwards.
10. Assemble a straight reducer union on the L-union connection aligned as above.
11. Connect the malfunction pressure safety device to the reducer union.
12. Connect the first and last slave extinguishing agent containers using the flexible pilot
hose.
5.4.5 Electrical release device QRV Assembly
WARNING Risk of injury due to escaping extinguishing agent
Assembly of the release device with a release pin in the activated position causes the quick release
valve to open immediately. This results in a risk of serious injury and substantial property damage.
• Before assembling the release device, you must ensure that the release pin is in the not activated
• Before assembling the release device, you must ensure that the extinguishing agent cylinder is
• Immediately vacate the suppression zone in case of faulty release.
• Inform all persons working in the installation zone about the risk of faulty release.
For assembly, only use the intended wrench flat and a suitable tool, e.g.a torque
wrench.
1. Pay attention to the instructions on the release device.
2. Check that the connection thread is undamaged and free of contamination.
84
position.
securely fastened and that the extinguishing agent line is connected to the valve output.
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en