This chapter only describes visual checks, functional tests and manual releases or resets. The num-
bering listed in "Table: Activities in servicing and maintenance" on page 155 is based on the activ-
ities to be carried out as per the "Service log for inert-gas extinguishing systems", in which the
servicing tasks must be documented.
Functional tests can usually be carried out per extinguishing zone so that all components are actu-
ated at least once.
Comprehensive servicing includes the following steps in addition to the full system test:
•
proper log-in/log-off of work with the operator
•
checking of the system specifics and changes and comparison against the log book
•
confirmation of the work and the operational state of the system by an authorized signatory of
the operator
•
documentation of changes or repairs as requested by the operator
In the event of a claim, undocumented deviations from the original or maintenance
may represent a high risk with regard to a clear issue of liability. For this reason, seam-
less documentation throughout the life cycle of the complete system is a prerequisite,
in the log book as well as in the service log.