Inert gas extinguishing system
Table of Contents

Advertisement

Handling packaging materials
Dispose of packaging materials in accordance with the respectively valid statutory regulations
and local guidelines.
NOTICE Improper disposal poses an environmental hazard
Packaging materials are valuable raw materials and in many cases, they can be reused, or they
can be effectively treated and recycled. Improper disposal of packaging materials causes envi-
ronmental hazards.
• Dispose of packaging materials in an environmentally responsible manner.
• Comply with locally applicable disposal guidelines. If necessary, commission a specialized

3.4 Storage

Storing extinguishing agent containers
Store reserve extinguishing agent cylinders under the following conditions:
Do not store outdoors.
Store in a dry, dust-free environment.
Do not expose to aggressive media.
Protect against direct exposure to sunlight.
Avoid mechanical vibrations/shocks.
Avoid condensation moisture.
Storage temperature: -4 to +131 °F (-20 to +55 °C).
Store with the valve protection cap in place.
Always store in the supplied transport frame or lying on the supplied pallet.
Observe national regulations on the storage of extinguishing agent cylinders.
If stored for more than 3 months, regularly check the general condition of all extinguishing
agent cylinders. If necessary, contact an authorized distributor or service personnel autho-
rized by the authorized distributor and have damaged or corroded extinguishing agent
containers replaced. Contact via the manufacturer if possible.
34
company to dispose of packaging.
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en