Viking Oxeo Installation And Maintenance Manual page 179

Inert gas extinguishing system
Table of Contents

Advertisement

Safety goggles
Safety gloves
Safety footwear
10.1.1Taking the system out of service
Prior to starting the disassembly process, the complete system must be taken out of service elec-
trically and mechanically.
1. Take the electric control device or fire detection and suppression control panel out of service
and secure it against restart.
2. Electrically disconnect the power supply unit and battery (rechargeable).
3. Remove the electrical release device from the pilot cylinder.
4. Remove the pneumatic pilot line - beginning with the pilot cylinders - up to the end of the
extinguishing agent container batteries.
5. Disassemble all system components in accordance with locally applicable occupational health
and safety and environmental protection directives.
10.1.2Dismantling the extinguishing agent containers
DANGER Risk of accidents due to heavy pressurized containers
Extinguishing agent containers are very heavy and may be pressurized. If handled improperly, they
can pose a life-threatening hazard.
• Always handle extinguishing agent containers with at least 2 people.
• Always use suitable means of transport.
• In the meantime, or as soon as possible, secure the valve outlet with a locking nut and the valve
with a protective valve cap.
• Wear safety gloves, safety footwear, protective goggles and hearing protection.
Inst. and Maint. Manual | Oxeo PR LCP | F_101921 Rev 02 | 10-2022 | en
WARNING Danger of a faulty release
173