T: Motor Tuning; T1: Induction Motor Auto-Tuning - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
S2-17
Sequence Timer 4 Stop
(3216)
Time
S2-18
Sequence Timer 4 Day
(3217)
Selection
S2-19
Sequence Timer 4
(3218)
Selection
S2-20
Sequence Timer 4
(3219)
Reference Source
u

T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance. When the drive is not accessible,
the current values of these parameters are not accessible. The default values are set by the Bypass Controller when a Bypass
Control Parameter Initialize (Z1-01 = 1, 2, or 3) command is given.
u

T1: Induction Motor Auto-Tuning

No.
(Addr.
Name
Hex)
T1-00
Motor 1/Motor 2 Selection
(0700)
T1-01
Auto-Tuning Mode
(0701)
Selection
<1>
T1-02
Motor Rated Power
(0702)
T1-03
Motor Rated Voltage
(0703)
T1-04
Motor Rated Current
(0704)
T1-05
Motor Base Frequency
(0705)
T1-06
Number of Motor Poles
(0706)
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
LCD Display
Sets the stop time for timer 4. The value must be set greater than
Tmr 4 Stop Time
or equal to S2-16.
Tmr 4 Day Sel
Sets the days for which sequence timer 4 is active.
0: Timer disabled
0: Timer disabled
1: Daily
1: Daily
2: Mon - Fri
2: Mon - Fri
3: Sat - Sun
3: Sat - Sun
4: Monday
4: Monday
5: Tuesday
5: Tuesday
6: Wednesday
6: Wednesday
7: Thursday
7: Thursday
8: Friday
8: Friday
9: Saturday
9: Saturday
10: Sunday
10: Sunday
Tmr 4 Seq Sel
Sets the action that occurs when sequence timer 4 is active.
0: Digital Out Only
0: Digital output only
1: Run
1: Run
2: Run - PI Disable
2: Run - PI disable
Selects the frequency reference source used for running the drive
Tmr 4 Ref Source
when sequence timer 1 is active (only applicable when S2-04 is
0: Operator (d1-01)
set to 1 or 2).
1: Operator (d1-02)
0: Operator (d1-01)
2: Operator (d1-03)
1: Operator (d1-02)
3: Operator (d1-04)
2: Operator (d1-03)
4: Terminals
3: Operator (d1-04)
5: Serial Com
4: Terminals
7: Pulse input
5: Serial communication
7: Pulse input
1: Motor 1
2: Motor 2
2: Stationary Auto-Tuning for Line-to-Line Resistance
3: Rotational Auto-Tuning for V/f Control Energy Saving
Sets the motor rated power as specified on the motor nameplate.
Note:
Use the following formula to convert horsepower into kilowatts:
1HP = 0.746 kW.
Sets the motor rated voltage as specified on the motor nameplate.
Sets the motor rated current as specified on the motor nameplate.
Sets the rated frequency of the motor as specified on the motor nameplate.
Sets the number of motor poles as specified on the motor nameplate.
Description
Description
B.12 S: Special Application
Values
Page
Default: 00:00
Min.: 00:00
Max.: 24:00
Default: 0
Range: 0 to 10
Default: 0
Range: 0 to 2
Default: 0
Range: 0 to 5; 7
Values
Page
Default: 1
Range: 1, 2
Default: 2
Range: 2, 3
<2>
Default:
Min.: 0.00 kW
Max.: 650.00 kW
Default: 200.0 V
<3>
Min: 0.0
<3>
Max: 255.0
<2>
Default:
Min.: 10% of drive
rated current
Max.: 200% of
drive rated current
Default: 60.0 Hz
Min.: 0.0
Max.: 240.0
Default: 4
Min.: 2
Max.: 48
155
155
156
156
79
79
79
B
79
80
80
80
273

Advertisement

Table of Contents
loading

Table of Contents