DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
VFD FREQUENCY REFERENCE
VFD OUTPUT FREQUENCY
FAULT: FB02 BAS Ilock Open
Figure 5.58 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault
DAMPER ACTUATOR OUTPUT
VFD FREQUENCY REFERENCE
VFD OUTPUT FREQUENCY
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
VFD RUN COMMAND
1 t
VFD RUN COMMAND
BAS INTERLOCK INPUT
Z1-14 Run Delay Fref
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 1 (Enable)
Z1-14 Run Delay Fref = 30.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
Figure 5.59 Run Delay with Preset Speed Example: Preset Speed
Z1-15 Interlck Wait Tm
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 10.0 sec
t1
t2
t3
t4
5.13 Z: Bypass Parameters
2 t
t3
5
167