YASKAWA P1000 Technical Manual page 347

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

Register No.
8400H
BYP Command
8401H
BYP Freq Ref
<5>
BYP DI-oo Command
8402H
8403H
BYP DO-oo Command
8404H
Time Set HHMM
8405H
Date Set Year
8406H
Date Set MMDD
8407H
Set RTC
8408H to 843FH
Reserved
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Contents
Bypass Command. Logically OR'd with the physical inputs
XXXXXXXX
Bypass Frequency Reference. This value is sent to the drive if selected by Bypass parameter Z1-07.
The units are determined by drive parameter o1-03.
Bypass Digital Input Command. These bits are logically OR'd with the physical inputs
XXXXXXXX
XXXXXXXX
Bypass Digital Output Command. These bits allow the digital outputs to be set over a network if
the corresponding digital output function is unused.
XXXXXXXX
XXXXXX
Time Set Hours and Minutes. Format is HHMM where HH is hours from 00 to 23 and MM is
minutes from 00 to 59. When new HHMM is set to RTC, the seconds will be set to a value of 0.
Date Set Year. Format is YYYY where YYYY is the four digit year from 2000 to 2099.
Date Set Month and Day. Format is MMDD where MM is month from 01 to 12 and DD is day
from 01 to 31.
The date and time values in registers 8404H to 8406H are written to the real time clock (RTC) in
the HOA operator connected to the bypass.
0: Do not write values to RTC
1: Write values to RTC
D.9 MEMOBUS/Modbus Data Table
XXXXXXXX
X
Run
X
Run Rev
X
Not Used
X
Transfer to Bypass
X
Smoke Purge Bypass
X
Smoke Purge Drive
X
Motor OR Select
X
Motor AND Select
X
Not Used
X
HAND Select
X
AUTO Select
X
DRIVE Select
X
BYPASS Select
X
Fault Reset
X
External Fault (EFB)
X
Not Used
XXXXXXXX
X
DI-1 (0/1 for Off/On)
X
DI-2
X
DI-3
X
DI-4
X
DI-5
X
DI-6
X
DI-7
X
DI-8
Not Used
XXXXXXXX
X
Not Used (0/1 for Off/On)
X
Not Used
X
Not Used
X
Not Used
X
Not Used
X
Not Used
X
DO-7
X
DO-8
X
DO-9
X
DO-10
X
Not Used
D
347