YASKAWA P1000 Technical Manual page 213

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

HOA Keypad Display
oPE05
Cause
Frequency reference is assigned to an option card
(Z1-07) and an input option card is not connected
to the drive
The Run command is assigned to an option card
(Z1-08) and an input option card is not connected
to the drive
HOA Keypad Display
oPE07
Cause
At least two analog input terminals are set to the
same function (i.e., at least two of these parameters
have the same setting: H3-02 or H3-10)
The following simultaneous contradictory
settings:
H3-02 or H3-10 = C (PI Target Value) while
b5-18 = 1 (enables b5-19 as the target PI value)
HOA Keypad Display
oPE09
Cause
The following simultaneous contradictory settings
have occurred:
• b5-15 is not set to 0.0 (PI Sleep Function
Operation Level)
• The stopping method is set to either DC
Injection Braking or coast to stop with a timer
(b1-03 = 2 or 3)
b5-01 is set to 1, enabling PI control, but the lower
limit for the frequency reference (d2-02) is not set
to 0 while reverse output is enabled (b5-11 = 1)
b5-01 is set to 3, enabling PI control, but the lower
limit for the frequency reference (d2-01) is not 0.
Parameter d2-01 is not accessible.
HOA Keypad Display
oPE10
Cause
V/f pattern setting error
HOA Keypad Display
oPE11
Cause
The following simultaneous contradictory settings
have occurred: C6-05 > 6 and C6-04 > C6-03
(carrier frequency lower limit is greater than the
upper limit)
If C6-05 ≤ 6, the drive operates at C6-03
The upper and lower limits between C6-02 and
C6-05 are contradictory
<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Run Command/Frequency Reference Source Selection Error
Reconnect the input option card to the drive.
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and PI functions
conflict.
Change the settings to H3-02 and H3-10 so that functions no longer conflict.
Note:
Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02 and H3-10
simultaneously.
Disable one of the PI selections.
PI Control Selection Fault
PI control function selection is incorrect. Requires that PI control is enabled (b5-01 = 1 or 3).
• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
Correct the parameter settings.
Correct the parameter settings.
V/f Data Setting Error
Set E1-03 to the pattern that fits the application.
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Correct the parameter settings.
<1>
6.6 Programming Errors
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
6
213