5.7 H: Terminal Functions
n
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way
as parameters H3-03 and H3-04 for analog input A1.
No.
H3-11
H3-12
n
H3-13: A1/A2 Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter prevents erratic drive control when using a "noisy" analog reference. Drive operation becomes more
stable as the programmed time becomes longer, but it also becomes less responsive to rapidly changing analog signals.
No.
H3-13
n
H3-14: Analog Input Terminal Enable Selection
When one of the multi-function digital input parameters is set for "Analog input enable" (H1-oo = C), the value set to H3-14
determines which analog input terminals are enabled when the input is closed. All of the analog input terminals will be enabled
all of the time when H1-oo≠ C. The terminals not set as the target are not influenced by input signals.
No.
H3-14
Setting 1: A1 Only Enabled
Setting 2: A2 Only Enabled
Setting 3: A1 and A2 Only Enabled
Setting 4: A3 Only Enabled
Setting 5: A1 and A3 Only Enabled
Setting 6: A2 and A3 Only Enabled
Setting 7: All Analog Input Terminals Enabled
n
H3-16 to H3-18: Terminal A1/A2/A3 Offset
Set the offset level of the selected input value to terminals A1, A2, or A3 that is equal to 0 Vdc input. These parameters rarely
require adjustment.
No.
H3-16
H3-17
H3-18
n
Multi-Function Analog Input Terminal Settings
See
Table 5.24
for information on how H3-02 and H3-10 determine functions for terminals A1 and A2.
Note:
The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting
and adjusting analog input functions.
Setting
0
Frequency Bias
1
Frequency Gain
128
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Name
A1/A2 Input Filter Time Constant
Name
Analog Input Terminal Enable Selection
Name
Terminal A1 Offset
Terminal A2 Offset
Terminal A3 Offset
Table 5.24 Multi-Function Analog Input Terminal Settings
Function
Page
Setting
129
2
Auxiliary Frequency Reference 1
129
3
Auxiliary Frequency Reference 2
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0.00 to 2.00 s
Setting Range
1 to 7
Setting Range
-500 to 500
-500 to 500
-500 to 500
Function
Default
100.0%
0.0%
Default
0.03 s
Default
7
Default
0
0
0