Setting
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Overtorque/Undertorque Detection Level
8
Stall Prevention Level During Run
9
Output Frequency Lower Limit Level
B
PID Feedback
C
PID Setpoint
<1> Setting 1F is "HAND Reference" in bypass controller software versions VST800298 and later. Setting 1F is "Not Used (Through Mode)" in bypass
controller software versions VST800297 and earlier.
Setting 0: Frequency Bias
The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency
reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also
when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference
by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input
terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.
Setting 1: Frequency Gain
The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog
input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.
Setting 2: Auxiliary Reference 1
Sets the auxiliary frequency reference 1 when multi-step speed operation is selected.
page 106
for details.
Setting 3: Auxiliary Reference 2
Sets the auxiliary frequency reference 2 when multi-step speed operation is selected.
page 106
for details.
Setting 4: Output Voltage Bias
Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available
only when using V/f Control.
Setting 5: Accel/Decel Time Gain
Adjusts the gain level for the acceleration and deceleration times set to parameters C1-01 through C1-08.
The drive acceleration time is calculated by multiplying the gain level to C1-oo as follows:
C1-oo × Accel/decel time gain = Drive accel/decel time
Setting 6: DC Injection Braking Current
The current level used for DC Injection Braking is set as a percentage of the drive rated current.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Function
100%
50%
20%
10%
0
5 V
10 V
1V 2V
Figure 5.37 Accel/Decel Time Gain with Analog Input Terminal
Page
Setting
129
D
Frequency Bias
129
E
Motor Temperature (PTC Input)
129
F
Not used
130
16
Differential PI Feedback
130
<1>
HAND Reference
1F
130
25
Secondary PID Setpoint
130
26
Secondary PID Feedback
130
Acceleration/deceleration gain from 1 to 10 V
(10 V)
× 10 (%)
=
Input Voltage (V)
5.7 H: Terminal Functions
Function
Refer to Multi-Step Speed Selection on
Refer to Multi-Step Speed Selection on
Page
130
130
130
130
131
131
131
5
129