YASKAWA P1000 Technical Manual page 163

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

0 to 10 V
2 k
Figure 5.55 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Current Input
Input terminals, A1, A2, and A3 can accept a current input signal.
Table 5.29 Analog Input Settings for Frequency Reference Using a Current Signal
Terminal
Signal Level
4 to 20 mA
A1
0 to 20 mA
4 to 20 mA
A2
0 to 20 mA
4 to 20 mA
A3
0 to 20 mA
Figure 5.56 Setting the Frequency Reference as a Current Signal to Terminal A2
Switching between Main/Auxiliary Frequency References
The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs.
to Multi-Step Speed Selection on page 106
Setting 2: BACnet or MEMOBUS/Modbus Communications
This setting requires entering the frequency reference via the RS-485 serial communications port (control terminals TXRX+
and TXRX-).
Refer to MEMOBUS/Modbus Configuration on page 326
Setting 3: Option Card
This setting requires entering the frequency reference via an option board plugged into connector CN5 on the bypass control
board. Consult the option card manual for instructions on integrating the drive with the communication system.
n
Z1-08: Run Command Select
Determines the source of the Auto Mode RUN command used by the Bypass Controller.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Drive
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
Signal Level
Function Selection
Selection
H3-01 = 2
(Frequency Reference Bias)
H3-01 = 3
H3-09 = 2
(Frequency Bias)
H3-09 = 3
H3-05 = 2
(Frequency Reference Bias)
H3-05 = 3
Jumper S1
A1/A2/A3
Voltage/Current
Selection
A1 A2 A3
0 or 4 to 20 mA
for details on using this function.
+10 V
4 k
Customer
+/- 10 V
Supply
OR
-10 V
Common
Parameter Settings
Gain
H3-02 = 0
H3-03
H3-10 = 0
H3-11
H3-06 = 0
H3-07
Drive
V
I
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
for instructions.
5.13 Z: Bypass Parameters
Drive
+V 10.5 V, 20 mA power supply
-10 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
Bias
H3-04
Set jumper S1 on the terminal
H3-12
board to "I" for current input.
H3-08
Notes
5
Refer
163

Advertisement

Table of Contents
loading

Table of Contents