Troubleshooting Without Fault Display; Troubleshooting Without Fault Display; Common Problems; Cannot Change Parameter Settings - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

6.9

Troubleshooting without Fault Display

This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor.
Performance Fine-Tuning on page 186
• Motor hunting and oscillation
• Poor motor torque
• Poor speed precision
• Poor motor torque and speed response
• Motor noise
u

Common Problems

Cannot Change Parameter Settings

Motor Does Not Rotate Properly after Pressing the AUTO
Button or after Entering External Run Command
Motor is Too Hot
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Motor Stalls During Acceleration or With Large Loads
Drive Frequency Reference Differs from the Controller Frequency Reference Command
Excessive Motor Oscillation and Erratic Rotation
Deceleration Takes Longer Than Expected
Noise From Drive or Motor Cables When the Drive is Powered On
Ground Fault Circuit Interrupter (GFCI) Trips During Run
Connected Machinery Vibrates When Motor Rotates
PI Output Fault
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)
Output Frequency is not as High as Frequency Reference
Sound from Motor
Motor Does Not Restart after Power Loss
u
Cannot Change Parameter Settings
Cause
The drive is running the motor
(i.e., the Run command is present).
The operator is not in the Parameter Setup Mode
(the screen will display "PAr").
A multi-function contact input terminal is set to allow
or restrict parameter editing
(H1-01 through H1-07 = 1B).
The wrong password was entered.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
for guidance on troubleshooting.
Common Problems
Motor Does Not Rotate
Motor Rotates in the Opposite Direction from the Run
Command
Motor Rotates in One Direction Only
Unexpected Noise from Connected Machinery
Oscillation or Hunting
• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.
• See what mode the operator is currently set for.
• Parameters cannot be edited when in the Setup Mode ("STUP"). Switch modes so that "PAr"
appears on the screen.
Refer to The Drive and Programming Modes on page
• When the terminal is open, parameters cannot be edited.
• Turn on the multi-function contact input set to 1B.
• If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
• Reset the password.
If you cannot remember the password:
Scroll to Z1-02. Press
• Set a new password to parameter Z1-03.

6.9 Troubleshooting without Fault Display

Possible Solutions
OFF
and
simultaneously. Parameter Z1-03 will appear.
Refer to Motor
Page
219
220
221
221
221
221
222
222
223
223
223
223
223
223
224
224
224
224
225
6
66.
219

Advertisement

Table of Contents
loading

Table of Contents