YASKAWA P1000 Technical Manual page 130

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

5.7 H: Terminal Functions
DC Injection Braking Current Level
100%
Drive Rated
Current
0
10 V
(4)
(20 mA)
Figure 5.38 DC Injection Braking Current Using an Analog Input Terminal
Setting 7: Torque Detection Level
Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog input.
The analog input replaces the level set to L6-02. An analog input of 100% (10 V or 20 mA) sets a torque detection level equal
to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection level settings are required.
Refer to L6: Torque Detection on page 142
for details on torque detection.
Setting 8: Stall Prevention Level
Allows an analog input signal to adjust the Stall Prevention level.
Figure 5.39
shows the setting characteristics. The drive will
use the lower value of the Stall Prevention level set to L3-06 or the level coming from the selected analog input terminal.
Stall Prevention Level during Run
100%
30%
Analog Input Level
0
30%
100%
Figure 5.39 Stall Prevention During Run Using an Analog Input Terminal
Setting 9: Output Frequency Lower Limit Level
The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID Feedback
Supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Refer to PID Feedback Input
Methods on page
92.
Setting C: PID Setpoint
Supplies the PID setpoint value and makes the frequency reference selected in parameter b1-01 no longer the PID setpoint.
PID operation to be enabled in b5-01 to use this setting.
Refer to PID Setpoint Input Methods on page
91.
Setting D: Frequency Bias
The input value of an analog input set to this function will be added to the frequency reference. This function can be used with
any frequency reference source.
Setting E: Motor Temperature
In addition to motor overload fault detection oL1, it is possible to use a PTC (Positive Temperature Coefficient) thermistor
for motor insulation protection.
Setting F: Not used
When set to F, an input does not affect any drive function, but the input level can still be read out by a PLC via a BACnet
communication or MEMOBUS/Modbus communications.
Setting 16: Differential PID Feedback
If an analog value is set for this function, the PID controller is set for differential feedback. The difference of the PID feedback
input value and the differential feedback input value builds the feedback value used to calculate the PID input.
Refer to PID
Feedback Input Methods on page
92.
130
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual

Advertisement

Table of Contents
loading

Table of Contents