Broadcast Messages; Fault Trace Contents - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

D.9 MEMOBUS/Modbus Data Table
Register No.
8440H
Time HHMM
8441H
Date Year
8442H
Date Mo Day MMDD
8443H to 84FFH
Reserved
8490H
Product Type Code
8491H
Product Type Code
BYP Parameters and
8500H to 87FFH
Monitors
8800H to FFFFH
Reserved
<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for
a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor capacity is
higher than 11 kW.
Refer to Power Ratings on page
<4> Set the number of motor poles to parameter E2-04 or E5-05 depending on the motor being used.
<5> Disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.
u

Broadcast Messages

Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.
Digital Input Command
bit 0
bit 1
bit 2, bit 3
bit 4
0001H
bit 5
bit 6 to B
bit C
bit D
bit E
bit F
0002H
Frequency Reference
u

Fault Trace Contents

The table below shows the drive fault codes that can be read out by MEMOBUS/Modbus commands from the U2-oo monitor
parameters.
Fault Code
0002H
Undervoltage (Uv1)
0003H
Control Power Supply Undervoltage (Uv2)
0004H
Soft Charge Circuit Fault (Uv3)
0006H
Ground Fault (GF)
0007H
Overcurrent (oC)
0008H
Overvoltage (ov)
0009H
Heatsink Overheat (oH)
000AH
Heatsink Overheat (oH1)
000BH
Motor Overload (oL1)
348
Time Hours and Minutes. Reads current time. Format is HHMM where HH is hours from 00 to 23
and MM is minutes from 00 to 59. Reads 0x0000 when no RTC option
Date Year. Reads current date. Format is YYYY where YYYY is the year from 0000 to 9999.
Reads 0x0000 when there is no RTC option.
Date Month and Day. Reads current date. Format is MMDD where MM is month from 01 to12
and DD is day from 01 to 31. Reads 0x0000 when there is no RTC option
Z1-oo, Z2-oo, Z3-oo, Z4-oo , UB-oo.
addresses.
240.
Forward Run (0: Stop 1: Run)
Direction Command (0: Forward, 1: Reverse)
Reserved
External Fault
Fault Reset
Reserved
Multi-Function Digital Input S5
Multi-Function Digital Input S6
Multi-Function Digital Input S7
Reserved
30000/100%
Table D.3 Fault Trace / History Register Contents
Fault Name
Contents
Refer to Parameter List on page 251
Contents
Fault Code
000CH
Drive Overload (oL2)
000DH
Overtorque Detection 1 (oL3)
0010H
Braking Resistor Overheat (rH)
0011H
External Fault at Input Terminal S3 (EF3)
0012H
External Fault at Input Terminal S4 (EF4)
0013H
External Fault at Input Terminal S5 (EF5)
0014H
External Fault at Input Terminal S6 (EF6)
0015H
External Fault at Input Terminal S7 (EF7)
001BH
Input Phase Loss (PF)
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
for Modbus
Fault Name