No.
Z4-05
Z4-06
Z4-07
Z4-08
n
Z4-09 to Z4-12: Gateway Address 1 to 4
Sets the network gateway address. Z4-09 is the most significant octet of the network gateway address; Z4-12 is the least
significant.
No.
Z4-09
Z4-10
Z4-11
Z4-12
n
Z4-13: Address Startup Mode
Selects the option address setting method.
No.
Z4-13
Setting 0: User-Defined (Static IP)
Setting 1: BOOTP
Setting 2: DHCP
n
Z4-14: Duplex Mode Setting
No.
Z4-14
Setting 0: Forced Half Duplex
Setting 1: Auto Negotiate Duplex Mode and Communication Speed
This setting also auto-negotiates Z4-15, Speed Mode Setting.
Setting 2: Forced Full Duplex
n
Z4-15: Speed Mode Setting
No.
Z4-15
Setting 10: 10 Mbps
Setting 100: 100 Mbps
n
Z4-16: Timeout
Sets the Control Connection Timeout value for detection of communication loss in tenths of a second. A value of 0 disables
the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
No.
Z4-16
n
Z4-17 to Z4-22: Scaling Factors
These parameters define scaling factors for drive monitors in the ODVA AC/DC Drive Object (Class 2AH), Instance 1, and
the attribute given below:
Speed Scale is attribute 22
Current Scale is attribute 23
Torque Scale is attribute 24
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Parameter Name
Subnet Mask 1
Subnet Mask 2
Subnet Mask 3
Subnet Mask 4
Parameter Name
Gateway Address 1
Gateway Address 2
Gateway Address 3
Gateway Address 4
Name
Address Startup Mode
Name
Duplex Mode Setting
Name
Speed Mode Setting
Name
Timeout
5.13 Z: Bypass Parameters
Setting Range
0 to 255
Setting Range
0 to 255
Setting Range
0 to 2
Setting Range
0 to 2
Setting Range
10, 100
Setting Range
0 to 300 s
Default
255
255
255
0
Default
192
168
1
1
Default
2
Default
1
5
Default
10
Default
0 s