YASKAWA P1000 Technical Manual page 285

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Z1-11
(85D0) 2-Motor AND/OR
Function Select
Z1-12
(85D1) Run Delay Time
Z1-13
(85D2) Pre-Interlock Run
Select
Z1-14
(85D3) Run Delay Frequency
Reference
Z1-15
(85D4) Interlock Wait Time
Z1-16
Energy Savings Mode
(85D5)
Enable
Z1-17
(85D6) Energy Savings Mode
Frequency
Z1-18
(85D7) Energy Savings Mode
Output Current Level
Z1-19
Energy Savings Mode
(85D8)
Frequency Reference
Deadband
Z1-20
Energy Savings Mode
(85D9)
Output Frequency
Deadband
Z1-21
Energy Savings Mode
(85DA)
Output Current
Deadband
Z1-22
(85DB) Energy Savings Mode
Time
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
LCD Display
0: Disabled (ignore digital inputs)
1: Always use only motor 1
2: Always use only motor 2
3: Always use motors 1 AND 2
4: OR function motor selected by digital input in HAND and
AUTO modes
5: OR function use motor 1 in HAND mode and motor selected
by digital input in AUTO mode
6: OR function use motor 2 in HAND mode and motor selected
2-Mtr AND/OR Sel
by digital input in AUTO mode
7: AND/OR function motor selected (1, 2, or both) by (2) digital
inputs in HAND and AUTO mode
8: AND/OR function use motor 1 in HAND mode and motor
selected (1, 2, or both) by (2) digital inputs in AUTO mode
9: AND/OR function use motor 2 in HAND mode and motor
selected (1, 2, or both) by (2) digital inputs in AUTO mode
10: AND/OR function use motors 1 AND 2 in HAND mode and
motor selected (1, 2, or both) by (2) digital inputs in AUTO mode
Delays the drive or bypass Run from when commanded (after
RUN, RUN ENABLE, and RUN INTERLOCK are all asserted).
Run Delay Time
Allows running at a preset speed starting immediately upon a Run
command, ignoring the BAS Interlock Input. The drive frequency
reference stays at this preset speed until the Run Delay time
Pre Int Run Sel
(Z1-12) times out.
0: Disabled
1: Enable delay time only
Frequency used while delaying the Run command.
Run Delay Fref
Upon entering a Run command, the damper actuator output will
be asserted. When an input is programmed for Interlock and the
Interlck Wait
time set to this parameter is reached before the Interlock input
goes active, a fault will be declared.
A setting of 0.0 will never time out.
0: Disable
1: Enable (Freq)
2: Enable (Freq + Cur)
Enrgy Savings En
Note:
Sets the value of the drive frequency reference for use in
comparison to enter or exit Energy Savings mode.
Energy Freq
Allows system to switch when the output current rises above this
level of motor rated current for time specified in Energy Time.
Energy Iout Lvl
Sets the tolerance around the drive frequency reference value
during comparisons to enter or exit Energy Savings mode
Enrgy Fref Dbnd
Sets the tolerance around the drive output frequency value during
comparisons to enter or exit Energy Savings mode.
Energy Freq Dbnd
Sets the tolerance around the drive output current value during
comparisons to enter or exit Energy Savings mode as a percentage
Energy Iout Dbnd
of motor rated current.
Sets the time that the drive frequency reference and drive output
frequency must be within the set limits before transferring to
Energy Time
Energy Savings mode.
Description
Energy Savings will not function if the motor is
running in reverse.
B.14 Z: Bypass Parameters
Values
Page
Default: 0
Range: 0 to 10
Default: 0.0 s
Min.: 0.0
Max.: 300.0
Default: 0
Range: 0, 1
Default: 60.0
<2>
Hz
Min.: 0.0
Max.: 60.0
Default: 0.0 s
Min.: 0.0
Max.: 300.0
Default: 0
Range: 0 to 2
Default: 60.0
<2>
Hz
Min.: 0.0
Max.: 60.0
Default: 0.0%
Min.: 0.0
Max.: 100.0
Default: 0.5 Hz
<2>
Min.: 0.0
Max.: 5.0
Default: 0.5 Hz
<2>
Min.: 0.0
Max.: 5.0
Default: 15.0%
Min.: 0.0
Max.: 30.0
Default: 30 s
Min.: 10
Max.: 60000
165
165
165
166
166
169
169
169
170
B
170
170
170
285