F: Options; F: Options; F6: Drive/Bypass Communications - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.7 F: Options
F parameters control the communication between the drive and the bypass.
u

F6: Drive/Bypass Communications

No.
(Addr.
Name
Hex)
Communication Error
F6-01
Operation Selection
External Fault from Bypass
F6-02
Controller Detection
(03A3)
Selection
External Fault from Bypass
F6-03
Controller Operation
(03A4)
Selection
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Description
Selects the drive behavior when the drive detects a CE fault.
0: Ramp to Stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to Stop.
2: Fast-Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
4: Alarm (d1-04)
Selects when the drive should detect an EF0 fault issued by the bypass
controller.
0: Always detected
1: Only during run
0: Ramp to Stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to Stop.
2: Fast-Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm Only.
B.7 F: Options
Values
Page
Default: 1
114
Range: 0 to 4
Default: 0
114
Range: 0, 1
Default: 1
114
Range: 0 to 3
261
B

Advertisement

Table of Contents
loading

Table of Contents