YASKAWA P1000 Technical Manual page 256

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.3 b: Application
No.
(Addr.
Name
Hex)
b5-12
PID Feedback Loss
(1B0)
Detection Selection
b5-13
PID Feedback Loss
(1B1)
Detection Level
b5-14
PID Feedback Loss
(1B2)
Detection Time
b5-15
PID Sleep Function Start
(1B3)
Level
b5-16
PID Sleep Delay Time
(1B4)
b5-17
PID Accel/Decel Time
(1B5)
b5-18
PID Setpoint Selection
(1DC)
b5-19
PID Setpoint Value
(1DD)
b5-20
PID Setpoint Scaling
(1E2)
b5-34
(19F)
PID Output Lower Limit
b5-35
(1A0)
PID Input Limit
b5-36
PID Feedback High
(1A1)
Detection Level
b5-37
PID Feedback High
(1A2)
Detection Time
b5-38
PID Setpoint User Display
(1FE)
b5-39
PID Setpoint Display Digits
(1FF)
b5-40
Frequency Reference
(17F)
Monitor Content during PID
256
0: No fault. Digital output only. 0: DO Only - Always
1: Fault detection. Alarm output, drive continues operation. 1: Alarm - Always
2: Fault detection. Fault output, drive output is shut off. 2: Fault - Always
3: Digital Output Always 3: DO Only@PID Enbl
4: Feedback Loss Alarm 4: Alarm @ PID Enbl
5: Feedback Loss Fault 5: Fault @ PID Enbl
Sets the PID feedback loss detection level as a percentage of the maximum
output frequency.
Sets a delay time for PID feedback loss.
Sets the frequency level that triggers the sleep function.
Sets a delay time before the sleep function is triggered.
Sets the acceleration and deceleration time to PID setpoint.
0: Disabled
1: Enabled
Sets the PID target value as a percentage of the maximum output frequency
when b5-18 is set to 1.
Note:
Values set above b5-38 will be internally limited to b5-38
0: 0.01 Hz units
1: 0.01% units (100% = max output frequency)
2: RPM (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39, units based on b5-46 setting)
Sets the minimum output possible from the PID controller as a percentage of
the maximum output frequency.
Limits the PID control input (deviation signal) as a percentage of the maximum
output frequency. Acts as a bipolar limit.
Sets the PID feedback high detection level as a percentage of the maximum
output frequency.
Sets the PID feedback high level detection delay time.
Scales the PID units to the maximum output frequency.
0: No decimal places
1: One decimal place
2: Two decimal places
3: Three decimal places
0: Display the frequency reference (U1-01) after PID compensation has been
added.
1: Display the frequency reference (U1-01) before PID compensation has been
added.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Description
Values
Page
Default: 0
96
Range: 0 to 5
Default: 0%
Min.: 0
96
Max.: 100
Default: 1.0 s
Min.: 0.0
96
Max.: 25.5
Default: 0.0 Hz
Min.: 0.0
97
Max.: 400.0
Default: 0.0 s
Min.: 0.0
98
Max.: 25.5
Default: 0.0 s
Min.: 0.0
98
Max.: 6000.0
Default: 0
98
Range: 0, 1
Default: 0.00%
Min.: 0.00
98
Max.: 100.00
Default: 1
98
Range: 0 to 3
Default: 0.0%
Min.: -100.0
99
Max.: 100.0
Default: 1000.0%
Min.: 0.0
99
Max.: 1000.0
Default: 100%
Min.: 0
97
Max.: 100
Default: 1.0 s
Min.: 0.0
97
Max.: 25.5
Default: 10000
Min.: 1
99
Max.: 60000
Default: 2
99
Range: 0 to 3
Default: 0
99
Range: 0, 1