YASKAWA P1000 Technical Manual page 165

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

n
Z1-09: HAND Mode Drive Speed Reference
The speed reference used when the Drive is running in HAND mode.
No.
Z1-09
<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.
n
Z1-10: Smoke Purge Preset Frequency Reference
Sets the speed at which the drive will run when the Smoke Purge Drive input is active.
No.
Z1-10
<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.
n
Z1-11: 2-Motor AND/OR Function Select
No.
Z1-11
Setting 0: Disabled (Ignore Digital Inputs)
Setting 1: Always Use Only Motor 1
Setting 2: Always Use Only Motor 2
Setting 3: Always Use Motor 1 and Motor 2
Setting 4: OR Function Motor Selected by Digital Input in HAND and AUTO Modes
Setting 5: OR Function Uses Motor 1 in HAND Mode and Motor Selected by Digital Input in AUTO Mode
Setting 6: OR Function Uses Motor 2 in HAND Mode and Motor Selected by Digital Input in AUTO Mode
Setting 7: AND/OR Function Motor Selected (1, 2, or both) by (2) Digital Inputs in HAND and AUTO Modes
Setting 8: AND/OR Function Uses Motor 1 in HAND Mode and Motor Selected (1, 2, or both) by (2) Digital Inputs in
AUTO Mode
Setting 9: AND/OR Function Uses Motor 2 in HAND Mode and Motor Selected (1, 2, or both) by (2) Digital Inputs in
AUTO Mode
Setting 10: AND/OR Function Uses Motor 1 and Motor 2 in HAND Mode and Motor Selected (1, 2, or both) by (2) Digital
Inputs in AUTO Mode
n
Z1-12 to Z1-15: Run Delay with Preset Speed
Parameters Z1-12 to Z1-15 allow running the Bypass at a preset speed before the BAS Interlock Input is active and continuing
at the preset speed for a delay time after the BAS Interlock Input becomes active. Refer to
examples.
n
Z1-12: Run Delay Time
Delays the drive or bypass Run after RUN, RUN ENABLE, and RUN INTERLOCK are all asserted.
No.
Z1-12
n
Z1-13: Pre-Interlock Run Select
Allows running at a preset speed starting immediately upon entering a Run command, ignoring the BAS Interlock Input. The
drive frequency reference stays at this preset speed until the Run Delay Time (Z1-12) times out.
No.
Z1-13
Setting 0: Disabled
Setting 1: Enable Delay Time Only
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Name
HAND Mode Drive Speed Reference
Name
Smoke Purge Preset Frequency Reference
Name
2-Motor AND/OR Function Select
Name
Run Delay Time
Name
Pre-Interlock Run Select
5.13 Z: Bypass Parameters
Setting Range
<1>
0.0 to 60.0 Hz
10.0 Hz
Setting Range
<1>
0.0 to 60.0 Hz
10.0 Hz
Setting Range
0 to 10
Figure 5.57
to
Figure 5.60
Setting Range
0.0 to 300.0 s
Setting Range
0, 1
Default
<1>
Default
<1>
Default
0
5
for
Default
0.0 s
Default
0
165

Advertisement

Table of Contents
loading

Table of Contents