YASKAWA P1000 Technical Manual page 171

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

n
Z1-27: Phase Loss Brownout Voltage Level
Sets the brownout condition voltage level.
No.
Z1-27
n
Z1-28: Phase Loss Brownout Detection Time
Sets the time that the input voltage is continuously measured to be below the Brownout Voltage level before declaring a
brownout fault.
No.
Z1-28
n
Z1-29: Phase Loss Blackout Voltage Level
Sets the voltage level below which is considered a blackout condition.
No.
Z1-29
n
Z1-30: EF0 Fault Delay Time
Sets the time between declaring a drive fault and opening the drive and bypass contactors.
No.
Z1-30
n
Z1-31: Loss of Load Detection Enable
No.
Z1-31
Setting 0: Disable
Setting 1: Enable and Declare Fault
Setting 2: Enable and Alarm Only
n
Z1-32: Loss of Load Drive Frequency
Sets the value to which the drive output frequency must be equal to or greater than for the drive to detect a loss of load.
No.
Z1-32
<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.
n
Z1-33: Loss of Load Drive Output Current
Sets the value to which the drive output current must be equal to or less than for the drive to detect a loss of load.
No.
Z1-33
n
Z1-34: Loss of Load Drive Time
While in Drive mode, the Loss of Load detection conditions must be met for the length of time entered here before detecting
a loss of load.
No.
Z1-34
n
Z1-35: Loss of Load Bypass Output Current
The motor current must be equal to or less than this value to detect a loss of load.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Name
Phase Loss Brownout Voltage Level
Name
Phase Loss Brownout Detection Time
Name
Phase Loss Blackout Voltage Level
Name
EF0 Fault Delay Time
Name
Loss of Load Detection Enable
Name
Loss of Load Drive Frequency
Name
Loss of Load Drive Output Current
Name
Loss of Load Drive Time
5.13 Z: Bypass Parameters
Setting Range
0 to 150 V
Setting Range
0.0 to 300.0 s
Setting Range
0 to 150 V0
Setting Range
0.0 to 300.0 s
Setting Range
0 to 2
Setting Range
<1>
0.0 to 60.0 Hz
60.0 Hz
Setting Range
0.0 to 999.9 A
Setting Range
0.0 to 300.0 s
Default
98 V
Default
3.0 s
Default
0 V
Default
1.0 s
Default
0
5
Default
<1>
Default
0.0 A
Default
1.0 s
171