n
H3-05: Terminal A3 Signal Level Selection
Determines the function assigned to analog input terminal A3.
page 128
for a list of functions and descriptions.
No.
H3-05
Terminal A3 Signal Level Selection
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. See the explanation provided for H3-01.
124.
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc. See the explanation provided for H3-01.
on page
125.
Setting 2: 4 to 20 mA
Setting 3: 0 to 20 mA
n
H3-06: Terminal A3 Function Selection
Determines the function assigned to analog input terminal A3.
page 128
for a list of functions and descriptions.
No.
H3-06
n
H3-07, H3-08: Terminal A3 Gain and Bias Setting
Parameter H3-07 sets the level of the selected input value that is equal to 10 Vdc input at terminal A3 (gain).
Parameter H3-08 sets the level of the selected input value that is equal to 0 V input at terminal A3 (bias).
No.
H3-07
H3-08
n
H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or
current input.
No.
H3-09
Setting 0: 0 to 10 V with Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be limited to 0.
page
124.
Setting 1: 0 to 10 V without Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted.
page
125.
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
page 128
for a list of functions and descriptions.
No.
H3-10
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Name
Name
Terminal A3 Function Selection
Name
Terminal A3 Gain Setting
Terminal A3 Bias Setting
Name
Terminal A2 Signal Level Selection
Name
Terminal A2 Function Selection
Refer to Multi-Function Analog Input Terminal Settings on
Setting Range
0 to 3
Refer to Setting 0: 0 to 10 V with Zero Limit on page
Refer to Setting 1: 0 to 10 V without Zero Limit
Refer to Multi-Function Analog Input Terminal Settings on
Setting Range
0 to 26
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
Refer to Setting 0: 0 to 10 V with Zero Limit on
Refer to Setting 1: 0 to 10 V without Zero Limit on
Refer to Multi-Function Analog Input Terminal Settings on
Setting Range
0 to 26
5.7 H: Terminal Functions
Default
0
Default
2
Default
100.0%
0.0%
Default
0 to 3
2
Default
0
5
127