YASKAWA P1000 Technical Manual page 61

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

No.
Name
2
Bypass Status Display
3
Data Display
Frequency
Reference
4
<1>
Source
LOCAL/REMOTE
5
<2>
Display
Function Key 2
6
(F2)
Function Key 1
7
(F1)
<1> Displayed when in Frequency Reference Mode.
<2> Displayed when in Frequency Reference Mode and Monitor Mode.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Display
POWERUP Displayed when the bypass is powering up.
OFF
Displayed when no Run command is present and the safety circuit is closed.
WAIT_FOR
Displayed when Run is requested, the safety circuit is closed, and the bypass is waiting for Run input.
_RUN
SAFETY
Displayed when the safety circuit input is open.
OPEN
INTRLOCK
Displayed when a Run command is present, the safety circuit is closed, but the Interlock input is open.
OPN
PRE RUN
Displayed when the bypass is running in the Pre-Run State at the programmed frequency for the
DRIVE
programmed time.
RUN
Displayed when running in Drive Mode.
DRIVE
RUN
Displayed when running in Bypass Mode.
BYPASS
RMOT
Displayed when running in Remote Transfer.
XFER EN
SMOK PRG
Displayed when running in Smoke Purge Bypass.
BYP
SMOK PRG
Displayed when running in Smoke Purge Drive.
DRV
AUTO
Displayed when running in Auto Transfer, a fault was detected and switched to Bypass Mode.
XFER EN
ENRGY
Displayed when running in Energy Savings Mode
SAVEN
MTR
Displayed when fault is removed but motor is still ramping down.
STOPPING
FAULTED Displayed when a fault has been detected causing motor output contactors to open.
Displays specific data and operation data.
OPR
Displayed when the frequency reference source is the HOA keypad.
Displayed when the frequency reference source is the MEMOBUS/Modbus Communication Inputs
COM
of the drive.
OP
Displayed when the frequency reference source is an option card connected to the drive.
AI
Displayed when the function reference is assigned to an analog input.
OFF
Displayed when HAND mode is OFF.
RSEQ
Displayed when the run command is supplied from a remote source.
LSEQ
Displayed when the run command is supplied from the operator keypad.
RREF
Displayed when the run command is supplied from a remote source.
LREF
Displayed when the run command is supplied from the operator keypad.
DATA
F2
Pressing
scrolls to the next display.
F2
Pressing
scrolls the cursor to the right.
DRV/BYP Pressing
F2
toggles selection between Bypass Mode and Drive Mode.
HELP
F1
Pressing
displays the Help menu.
F1
Pressing
scrolls the cursor to the left.
HOME
F1
Pressing
returns to the top menu (Frequency Reference).
ESC
F1
Pressing
returns to the previous display.
Monitor
F1
Pressing
switches Monitor mode.
F1
Pressing
selects/deselects Drive Test Mode. Enters and exits Drive Test Mode when in Bypass
RLY
Mode (Open/Close K1).
4.2 Using the HOA Keypad
Content
4
61

Advertisement

Table of Contents
loading

Table of Contents