5.7 H: Terminal Functions
Setting
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock 1 (N.O.)
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
Setting 0: During Run
The output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
Setting 1: Zero Speed
The output closes when the output frequency or motor speed falls below the minimum output frequency set to E1-09 or b2-01.
Status
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
Setting 2: Speed Agree 1 (f
The output closes when the actual output frequency or motor speed is within the Speed Agree Width (L4-02) of the current
frequency reference regardless of the direction.
118
Function
OFF
ON
Run command
Baseblock
OFF
command
Output
frequency
OFF
ON
During Run
Figure 5.23 During Run Time Chart
Output frequency
OFF
Zero Speed
Figure 5.24 Zero-Speed Time Chart
/f
Agree 1)
ref
out
Page
Setting
120
17
Torque Detection 1 (N.C.)
120
1A
During Reverse
120
1B
During Baseblock 2 (N.C.)
121
1E
Restart Enabled
121
20
Drive Overheat Pre-Alarm (oH)
121
2F
Maintenance Period
121
37
During Run 2
121
39
Watt Hour Pulse Output
121
3D
During Speed Search
121
4C
During Fast Stop
121
4D
oH Pre-Alarm Time Limit
122
60
Internal Cooling Fan Alarm
122
100 to 160 Functions 0 to 60 with Inverse Output
Description
ON
Description
E1-09 (Min. Output Frequency) or
b2-01 (Zero Speed Level)
ON
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Function
Page
121
123
123
123
123
123
123
124
124
124
124
124
124