YASKAWA P1000 Technical Manual page 179

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

n
Z3-08, Z3-09: BACnet Device Object Identifier
These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09
is the most significant word.
No.
Z3-08
Z3-09
Example 1: Set Device Object Instance Identifier of "1234".
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of "123456".
123456 decimal is equal to 1E240H.
Set Z3-08 to D687H and set Z3-09 to 12H.
n
Z3-10: Cable Loss Pre-set Speed
When a serial communications fault is detected and Z3-05 = 4, the value here will become the frequency reference.
No.
Z3-10
n
Z3-11: Communication Fault Detection Selection
No.
Z3-11
Setting 0: Disabled
Ignore setting in Z3-05.
Setting 1: Enabled
Behavior defined by Z3-05.
n
Z3-12: Network Digital Input Select
Determines whether the serial communication digital input simulation is active.
Note:
Parameter available in bypass controller software versions VST800298 and later.
No.
Z3-12
Setting 0: Disable
Serial communications physical digital inputs are ignored.
For MEMOBUS/Modbus (Z3-01 = 0): Command Register 8402H is disabled.
For Metasys N2 (Z3-01 = 1): Binary Outputs B05, B06, B07, B08, and B09 are disabled.
For P1 Apogee (Z3-01 = 2): Points LDO44, LDO45, LDO46, LDO47, and LDO48 are disabled.
For BACnet (Z3-01 = 3): BV72, BV73, BV74, BV75, BV76, BV77, BV78, and BV79 are disabled.
Setting 1: Enable
Physical digital inputs S1 to S8 are logically OR'd with the serial communications digital inputs.
WARNING! Sudden Movement Hazard. Setting this parameter to 1 may cause the system to run unexpectedly or not stop when required
even if the physical digital input is de-energized, resulting in death or serious injury. Clear all personnel from the drive, motor and machine
area before applying power. Set this parameter to 0 to prevent serial communications from triggering undesired and unexpected system
operation.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Name
BACnet Device Object Identifier 0
BACnet Device Object Identifier 1
Name
Cable Loss Pre-set Speed
Name
Communication Fault Detection Selection
Name
Network Digital Input Select
5.13 Z: Bypass Parameters
Setting Range
0 to FFFFH
0 to 003FH
Setting Range
0.0 to 60.0 Hz
Setting Range
0 to 1
Setting Range
0, 1
Default
1
0
Default
0.0 Hz
Default
1
5
Default
0
179