A.2 Drive Specifications
Item
Momentary Power Loss
Ride-Thru
Heatsink Overheat Protection
Braking Resistor Overheat
Protection
Protection
Functions
Stall Prevention
Ground Protection
DC Bus Charge LED
Area of Use
Ambient Temperature
Humidity
Storage Temperature
Environment
Altitude
Vibration/Shock
Safety Standard
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors
and with changing motor temperature. Contact Yaskawa for consultation.
<2> Disable Stall Prevention during deceleration (L3-04 = 0) when using a regenerative converter, a regenerative unit, a braking resistor or the Braking
Resistor Unit. The default setting for the Stall Prevention function will interfere with the braking resistor.
<3> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed
down to zero in the shortest time.
<4> Actual specifications may vary depending on motor characteristics.
<5> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<6> May be shorter due to load conditions and motor speed.
<7> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
244
Immediately stop after 15 ms or longer power loss
Thermistor
Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Stall Prevention is available during acceleration, deceleration, and during run.
<7>
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
Indoors
-10 to +40 °C
95 RH% or less (no condensation)
-20 to +60 °C (short-term temperature during transportation)
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
Derating on page 248
for details.
2
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
(2A0004 to 2A0211 and 4A0002 to 4A0165)
2
2.0 m/s
(2A0250 to 2A0415 and 4A0208 to 4A0675)
UL 508C (Power Conversion), UL/cUL listed, CSA 22.2 No. 14-05 (Industrial Control Equipment), CE
marked, RoHS compliant, EN 61800-5-1 (LVD), EN 61800-3 (EMC), IEC60529
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual